Installation] Public sports facility comprehensive disaster prevention center oxygen concentration meter FIX800 O2 8ea electronic sign installation work

경기도 일산 · 2022.11.21

Applied Markets

Military Facilities Safety Other

Installed Gases

O2 (Oxygen)

Project Details

 Hello, this is RS Korea.  

The location where FIX800 will be installed today is the sports complex and gymnasium of the Gyeonggi public sports facility. 

 

 

Today's installation equipment. Gymnasium: FIX800 O2 3EA, electronic display + warning lights, warning lights (a warning light is installed at the rear entrance to indicate the inside situation) Sports Complex: FIX800 O2 5EA, electronic display + warning lights Installation points were divided into two days. What is combustion? When substances are oxygenated and combined, it is a phenomenon that produces a lot of light and heat. The fire extinguishing principle is divided into three types: suffocation fire extinguishing that blocks oxygen, cooling fire extinguishing that removes heat, and subcatalytic fire fighting that blocks chain reactions.

Source: Ministry of Employment and Labor, National Fire Agency In spaces where carbon dioxide fire extinguishing equipment is installed, oxygen concentration meters and carbon dioxide concentration meters must be installed and the measured values ​​managed to prevent suffocation, poisoning, and fatal accidents. There is a fire extinguishing agent room within the general disaster prevention center of the public sports facility where this construction was carried out, and cabinet-type fire extinguishers were installed in places that need to be protected first in case of fire, such as computer rooms, wireless power supplies (UPS), and servers. In this way, workplaces that handle gases related to 'suffocation fire extinguishing' such as fire extinguishing agents and cabinet-type automatic fire extinguishers have installed oxygen (O2) concentration meters and carbon dioxide (CO2) concentration meters in an environment where suffocation can occur even from a leak. There are a total of eight installation points in public institution sports facilities, including three gymnasiums and five sports complexes. There is a room with CO2 (carbon dioxide) used as a fire extinguishing agent and a cabinet-type fire extinguishing facility. It is scheduled to be installed in all sites where suffocation accidents are at risk, such as the general disaster prevention room, equipment room, computer room, chemical room, and electrical room.

First, it is a gymnasium.Previous imageNext iGymnasium Gas Meter Installation Points for installing FIX800, an installable measuring device within the gymnasium comprehensive pest control center, are the general disaster prevention room, electrical room, and fire extinguishing agent room.

This is the location of the warning light and electronic signboard installation. The electronic signboard and warning light were installed at the main entrance, and the warning light was connected to a separate entrance at the back so that the internal situation can be known.

The laying of wires was done neatly using 8C shielded cables, the same as during the actual shooting, and using line ducts for lighting. However, due to the nature of the space called a gymnasium, the moving and wiring distances were long, so the work time was slightly delayed.

Installation is in progress at each point. Installation of external warning lights includes work at heights.

Installation within the gym has been completed. The following are the installation points for the sports complex.

As with the gymnasium, we are in the process of installing an oxygen concentration meter FIX800 and an electronic display board in the disaster prevention room, equipment base, computer room, electric room, and fire extinguishing agent room, which are sites where suffocation accidents are a concern within the Sports Complex Disaster Prevention Center. 8C shielded cable was used for laying wires, line ducts for electric lights were used, and GW waterproof corrugated pipe was used to move wires between ducts and walls, and all were carried out in the same manner as during the actual inspection.

 

 

As with the gymnasium, power supply was carried out without any additional electrical work by using a 220V outlet outside the entrance where the electronic display board was installed. Installation within the sports complex was completed. As always, product training was completed well. In the case of on-site work such as installation, unexpected variables may arise on site. Based on our experience in delivery and installation in various environments, RS Korea carefully checked the installation location (measurement environment) during the inspection to minimize this, and completed the product successfully without any variables. We have an official branch in Korea and are fully equipped with A/S repair, calibration gas facilities, and production and delivery systems, so we are a gas specialized company that includes calibration, repair, production, delivery, and installation in addition to simple sales.

RS Korea repair and inventory room has completed the installation of the installable oxygen meter FIX800 O2 0~30% at the comprehensive pest control center in the public sports facility in Ilsan. Today's blog summary Region: Gyeonggi-do Environment: Public facility gymnasium, comprehensive pest control center and fire extinguishing agent product in the sports complex: WANDI FIX800 O2 0~30% 8ea, warning lights, display board installation number of people: 4 people Takes 2.5 days (8 hours per day) Other information: - Work at heights using a ladder of about 2m - Power supply uses a 220V outlet outside the entrance, so no separate electrical work - Installation of wires using line ducts for lighting - Due to the nature of the space called a gymnasium, work time is delayed due to long moving and wiring distances - Moving wires between ducts and walls requires installation of a composite gas meter FIX800 O2 This concludes the blog on installing 0~30% warning lights and electronic display boards. If you have any inquiries regarding environmental measurements such as due diligence and gas meter installation, please contact the number below. ☎031-340-6952

This was RS Korea's ZOE. Thank you.