CONSTRUCTION CASE

RS Korea — FIX800 Five-Gas Detector and LED Display Installation, Telecom Branch Diesel Tank Room (Part 2, Wonju, Gangwon-do)

Wonju, Gangwon-do · 2025.07.03

Applied Markets

Wastewater

Installed Gases

CO (Carbon Monoxide) O2 (Oxygen) H2S (Hydrogen Sulfide) CO2 (Carbon Dioxide)

Project Details

RS Korea returned to a telecommunications company branch building in Wonju, Gangwon-do to complete an additional FIX800 five-gas detector installation, one level further underground than a previous project at the same site, following the client's satisfaction with earlier installations at both the Wonju and Dongjak-gu branches.

Purpose

This installation continues to satisfy Article 618 of Korea's Occupational Safety and Health Standards, requiring monitoring of five gases — O2, CO, CO2, H2S, and EX — in confined spaces to prevent worker asphyxiation.

가스측정기 전문 완디코리아 WANDI®

Equipment

가스측정기 전문 완디코리아 WANDI®

The equipment planned for installation was RS Korea's steady-selling FIX800 fixed multi-gas detector, capable of simultaneously measuring all five legally required gases, paired with a custom-built LED status board so gas concentration can be monitored from both inside and outside the workspace.

Installation Location

가스측정기 전문 완디코리아 WANDI®

The installation location was a diesel storage tank room. Diesel is a flammable liquid, and when it evaporates it becomes an explosive-hazard gas; in spaces with inadequate ventilation, a buildup of combustible gas can create an asphyxiation risk. The detector was mounted at the deepest point of the tank room, and the display board was installed directly above the entrance.

Before Installation

가스측정기 전문 완디코리아 WANDI®

A short but thorough toolbox meeting (TBM) was carried out. The team briefed the equipment to be installed, set up a safety sign board, and ran a blower to ventilate the space — a minor incident during a safety-installation project would be especially unfortunate.

가스측정기 전문 완디코리아 WANDI®

Before starting work, a portable IoT gas detector, the EDW500, was used to confirm the atmosphere was safe. The unit was then left on site, allowing gas conditions to be checked remotely via mobile device or web browser for reporting purposes.

During Installation

가스측정기 전문 완디코리아 WANDI®

The display board was installed first, with ladder work always carried out by a two-person team. The detector was then installed in a notably cramped space due to the tank's footprint; the corner location received little natural light, so work lighting was used throughout — essential in any environment where floor obstructions or other hazards could otherwise cause an accident.

가스측정기 전문 완디코리아 WANDI®

Cable runs used waterproof corrugated conduit. Elevated work above a certain height requires a safety ladder and a harness at all times.

After Installation

가스측정기 전문 완디코리아 WANDI®

Commissioning was carried out by introducing calibration gas to force an alarm condition, confirming that both the internal and external alarms activate simultaneously so workers can evacuate quickly in an emergency.

Closing

가스측정기 전문 완디코리아 WANDI®

The detector installed at this facility's original wastewater treatment room last year continues to operate normally, and this additional installation was completed successfully.

Project summary
Purpose: Five-gas monitoring under Article 618 of the Occupational Safety and Health Standards for confined-space asphyxiation prevention
Equipment: FIX800 fixed multi-gas detector (5-gas) with dedicated FIX-DS 5-channel display board
Location: Hazardous-substance storage tank room (diesel)
Crew: Two field technicians, one site supervisor
Duration: Approximately 3 hours, including material setup and toolbox meeting

#WastewaterTreatmentFacility #GasDetector #InstalledGasDetector #FixedGasDetector #MultiGasDetector #WastewaterGasDetector #WaterTreatmentGasDetector #OccupationalSafetyAndHealthAct #FiveGases #5Gases #5GASDetector #OSHAGasDetector #FixedMultiGasDetector #ConfinedSpaceGasDetector #Wandi #FIX800 #GasMonitoring #HazardousGas #HazardousMaterialManagement #StorageRoom #TankRoom

Other Cases

Back to List