Hello, this is our team at RS Korea.
Today we visited a public institution in Siheung after receiving an inquiry about installing an oxygen concentration detector inside a wastewater storage tank at their wastewater treatment facility.
Purpose of Installation
The goal was to measure the oxygen concentration inside the tank — which resembles the structure of a vinyl greenhouse — before cleaning work begins inside, for the safety of workers entering this confined space.
Installed Item
Given the characteristics of the environment, we built a custom pre-treatment unit using a stainless steel (SUS) enclosure with basic moisture removal.
The product used is the FIX800, a fixed-type gas detector.
Installation Process
The work proceeded in the following order: anchoring the pipe support for the pre-treatment unit; fixing the base of the SUS enclosure; mounting the enclosure alongside the pipe; connecting power from the nearby automatic control unit; and connecting the SUS sampling pipe into the storage tank.
The lower pipe was connected to draw the power line from the adjacent automatic control equipment.
With the enclosure mounted, we connected the SUS sampling pipe to measure the oxygen concentration inside the wastewater storage tank.
A laser level was used to ensure everything was properly aligned.
To prevent the thin stainless steel pipe from being accidentally crushed if a worker were to step on it, we reinforced it with a channel bracket and thicker steel piping for double protection.
This process was repeated six times, completing six sections of steel piping work.
After installation, we explained the pre-treatment process and calibration schedule to the facility manager, cleaned up the work area, and completed the project.
Even in cases where installing a detector directly is difficult, we design and build custom pre-treatment units tailored to the specific site conditions and environment. When gas measurement feasibility is unclear over the phone, we carry out an on-site survey to confirm the conditions accurately and test the setup before advising on the best approach.
Inquiries about detectors and installation are always welcome. RS Korea is a gas-detection specialist offering more than product sales alone — including in-house calibration, domestic repair service, custom manufacturing, and installation work. Drawing on experience across demonstrations, site surveys, deliveries, repairs, and installations in a wide range of environments, we provide tailored one-to-one solutions for each gas measurement environment.
자주 묻는 질문 (FAQ)
Q1. Why was an oxygen detector needed inside this wastewater storage tank?
Before workers enter the tank to clean it, the oxygen concentration must be verified to confirm the space is safe, since confined tanks like this one can develop oxygen-deficient conditions.
Q2. Why was a custom stainless steel enclosure and pre-treatment unit built for this site?
Given the specific environmental conditions of this tank, a stainless steel (SUS) enclosure with a basic moisture-removal pre-treatment unit was custom-built to allow reliable sampling and protect the equipment from the tank's conditions.
Q3. Why was the sampling pipe reinforced with additional steel piping?
The stainless steel sampling pipe is relatively thin and could be crushed if accidentally stepped on. A channel bracket and thicker steel pipe were added as double protection to prevent damage.
Q4. Can RS Korea handle sites where standard detector installation is difficult?
Yes. For environments where a detector cannot be installed directly, RS Korea designs and manufactures custom pre-treatment units suited to the specific site conditions, and conducts on-site surveys and testing beforehand to confirm feasibility.
Q5. What follow-up guidance is provided after installation?
After installation, our team explains the pre-treatment process and the recommended calibration cycle to the facility's staff before completing the project.
#ConfinedSpace #O2 #Oxygen #GasDetector #OxygenConcentrationDetector #PreTreatmentUnit #WastewaterTreatment #TankGasMeasurement #FIX800 #FixedOxygenDetector