CONSTRUCTION CASE

FIX800 Multi-Gas and CO Detector Installation for a Sewage Sludge Recycling Facility (Pohang)

Pohang · 2024.11.04

Applied Markets

Wastewater

Installed Gases

EX (Combustible) CO (Carbon Monoxide) O2 (Oxygen) H2S (Hydrogen Sulfide)

Project Details

Hello. This is RS Korea. Today we are sharing a recent installation of the FIX800 gas detector in Pohang. This project involved two related but slightly different types of installation carried out at a single site. Thank you for your interest.

Installation overview

Site: Pohang City Sewage Sludge Recycling Facility
Installation points and equipment:
- Sludge intake area: FIX800 (O2, H2S, EX), 1 set, with an outdoor status board
- Dried sludge storage tank: FIX800 (CO), with high-grade pre-treatment equipment and a self-supporting status board
Schedule: installed by two two-person teams in a single day

Before describing the installation, here is a brief background on what a sewage sludge recycling facility is.

가스측정기 전문 완디코리아 WANDI®

[Photo source: Sudokwon Landfill Management Corporation]

Put simply, sewage sludge is the combined food wastewater that drains from household sinks. A facility that processes this collected sludge through several stages to recover it as a resource is called a sewage resource recovery facility.

가스측정기 전문 완디코리아 WANDI®

The two points we installed equipment at this time are the locations circled in the image above.

1. Sludge intake area: after the intake process is completed, the shutter is lowered, turning this area into an enclosed space that is also filled with odor and explosive gas risk. A gas detector was installed here for the safety of workers entering the space.

가스측정기 전문 완디코리아 WANDI®

2. Dried-goods storage: this is the warehouse where the heat-treated dried material from the intake area is stored. The green urethane floor covers what is effectively one large tank. Flammable gases such as methane, generated from the dried sludge just before recycling, can ignite even from a small spark, so we installed a detector for CO, a representative combustion gas, to prepare for this fire risk.

가스측정기 전문 완디코리아 WANDI®

Because the installation points and power-supply method had already been agreed in several preliminary meetings, the work itself went smoothly on installation day.

가스측정기 전문 완디코리아 WANDI®가스측정기 전문 완디코리아 WANDI®가스측정기 전문 완디코리아 WANDI®

After completing safety training, the installation plan and sequence were briefed to the construction team and the site manager. The team then split into two two-person groups to carry out installation at both locations simultaneously.

1. Multi-gas detector installation at the sludge intake area

가스측정기 전문 완디코리아 WANDI®가스측정기 전문 완디코리아 WANDI®가스측정기 전문 완디코리아 WANDI®

1. After drilling into the concrete wall, the display board was installed first.
2. For power, the outlet originally used for the exhaust fan behind the wall was converted from a single outlet to a dual outlet, leaving a spare connection.
3. The detector was installed and the cable length was measured and cut.

가스측정기 전문 완디코리아 WANDI®가스측정기 전문 완디코리아 WANDI®가스측정기 전문 완디코리아 WANDI®

4. The cut cable ends were then terminated.
5. The cabling was neatly secured with cable saddles so as not to interfere with the existing facilities.
6. Finally, the display board and the FIX800 were connected to complete the installation.

가스측정기 전문 완디코리아 WANDI®가스측정기 전문 완디코리아 WANDI®가스측정기 전문 완디코리아 WANDI®

7. Once powered on, the detector displayed normal readings.
8. The outdoor status board also showed a normal (green) status.
9. An alarm test was carried out by introducing test gas, completing the installation cleanly.

2. CO detector installation at the dried sludge storage tank

(This location required a self-supporting stainless enclosure and pre-treatment equipment, so anchor work was carried out first.)

가스측정기 전문 완디코리아 WANDI®가스측정기 전문 완디코리아 WANDI®가스측정기 전문 완디코리아 WANDI®

1. Holes were drilled with a hammer drill to match the anchor bolt length.
2. The drilled area and surrounding dust were cleaned.
3. The waterproof coating around the drilled area, which can lift during drilling, was re-sealed.

가스측정기 전문 완디코리아 WANDI®가스측정기 전문 완디코리아 WANDI®가스측정기 전문 완디코리아 WANDI®

4. The anchors were installed and leveled.
5. Piping was installed to connect the gas in/out hoses to the front (positive pressure) and rear (negative pressure) sides of the blower; these ports had already been welded in place as agreed during the earlier meetings.
6. The pre-installed 220V power line and 4-20mA signal line were wired. Because the schedule did not align with the electrical team, permanent power was not available immediately, so a temporary test run was carried out using an auxiliary battery.

가스측정기 전문 완디코리아 WANDI®가스측정기 전문 완디코리아 WANDI®가스측정기 전문 완디코리아 WANDI®

7. A durable PTFE hose was connected to the completed piping.
8. Product training and usage guidance were provided to the person in charge.
9. And here is the finished installation. After this photo was taken, the conduit and gas line were tidied with cable ties, though unfortunately no photo was taken of that final step.

This project involved two slightly different types of installation carried out simultaneously at one site. Because all the details had already been coordinated in advance through a site survey and several meetings, the actual installation work was completed very simply — a good reminder of how valuable thorough preparation is.

This concludes our post on the FIX800 installation at the sewage sludge recycling facility in Pohang. If you have any questions about gas detectors or other environmental monitoring instruments, please feel free to contact our team.

This was RS Korea. Thank you for reading, and see you in the next post!

Frequently Asked Questions (FAQ)

Q1. What equipment was installed at this site and where?

At the sludge intake area of the Pohang sewage sludge recycling facility, we installed one FIX800 (O2, H2S, EX) unit with an outdoor status board; at the dried sludge storage tank, we installed a FIX800 (CO) unit with high-grade pre-treatment equipment and a self-supporting status board.

Q2. Why is a gas detector needed at the sludge intake area?

After the intake process is completed, the shutter is lowered and the area becomes an enclosed space filled with odor and explosive gas risk, so a detector is installed there to protect workers who enter.

Q3. Why is CO measured at the dried sludge storage tank?

Flammable gases such as methane, generated from dried sludge just before recycling, can ignite from even a small spark, so CO — a representative combustion gas — is measured to prepare for fire risk.

Q4. How long did the installation take?

Because the installation points and power-supply method were coordinated in advance through a site survey and several meetings, two two-person teams completed both installations simultaneously in a single day.

Q5. What happens if permanent power is not yet available on installation day?

If the schedule does not align with the electrical team and permanent power cannot be connected immediately, a temporary test run is carried out using an auxiliary battery.

#FIX800#SewageSludgeRecycling#ConfinedSpaceSafety#GasDetectorInstallation#COMonitoring#MultiGasDetector#EnvironmentalMonitoring#IndustrialSafety#WANDI#RSKorea

Other Cases

Back to List